HVAC duct sizing calculator
Any two of duct size (round or rectangular), airflow, velocity and friction rate. Round and rectangular equivalents, nearest standard sizes, friction loss per 100 ft (Darcy-Weisbach, Colebrook), velocity pressure, design checks. Equal-friction sizing, fixed-depth ducts, IP or SI. Shows every step with the numbers. $0.002 USDC per call.
Input
Sample response
Published by the provider. Your run returns a fresh response.
response18 keys
airflow1000
checks3 keys
aspect_rationull
friction"Typical design range (0.04-0.15 in. w.g./100 ft; about 0.3-1.2 Pa/m)."
velocity"Normal design range (400-2,500 FPM; about 2-12.7 m/s)."
friction_factor0.01885
friction_rate0.08
inputs_used2 keys
airflow1000
friction_rate0.08
next_calls1 item
0{ arguments, price, tool, … }4 keys
notes3 items
0"The rectangular size has the same friction loss and airflow as the round duct (ASHRAE equivalent diameter); its velocity is lower because its area is larger."
1"Galvanized steel (ε = 0.0003 ft) and standard air (0.075 lb/ft³, 70 °F, sea level). Fittings and transitions are not included."
2"For design guidance; the engineer of record is responsible for final selections."
primary_shape"round"
rectangular9 keys
area1.184
aspect_ratio1
basis"equal_friction"
equivalent_diameter14.27
friction_rate0.08
height13.06
standard_sizes[…]2 items
velocity845
width13.06
references2 items
0"ASHRAE Handbook—Fundamentals (2021), Ch. 21 Duct Design"
1"SMACNA HVAC Duct Design Manual (standard sizes, aspect ratio guidance)"
reynolds_number114361
round5 keys
area1.1112
diameter14.27
friction_rate0.08
standard_sizes[…]2 items
velocity900
solved_for"size"
steps3 items
0{ calculation, reference, step }3 keys
1{ calculation, reference, step }3 keys
2{ calculation, reference, step }3 keys
unit_labels17 keys
airflow"CFM"
area"ft²"
condensate"gal / h"
density"lb / ft³"
elevation"ft"
enthalpy"BTU / lb dry air"
friction_rate"in. w.g. / 100 ft"
grains"gr / lb dry air"
humidity_ratio"lb water / lb dry air"
length"in"
load"MBH (1,000 BTU/h)"
pressure"psia"
relative_humidity"%"
specific_volume"ft³ / lb dry air"
temperature"°F"
velocity"FPM"
velocity_pressure"in. w.g."
units"IP"
velocity900
velocity_pressure0.0505
responseobject, 18 keysYour agent can do this on its own
Add the MCP URL in Claude Code, Cursor or Codex. Your agent can run Tools within its spending limits, or ask for approval each time. Connect your agent
Connect your agent
Add one MCP URL and your agent can find and run this tool within its spending limits. Choose “Ask each time” if you want to approve every Call.
MCP URL
https://app.aecon.ai/mcpTerminalbash
In Claude Code, open /mcp, select agentic-economy, then choose Authenticate.
Track record
- Paid calls, last 30 days
- 2
- Buyers, last 30 days
- 2
- Last paid call
Reported by the x402 directory.